General Notes

The motor cable should be kept as short as possible in order to avoid
electromagnetic emission as well as capacitive currents.

Use of line filters in ungrounded systems is not recommended.

PowerFlex drives may cause radio frequency interference if used in a
residential or domestic environment. The user is required to take measures
to prevent interference, in addition to the essential requirements for CE
compliance listed below, if necessary.

Conformity of the drive with CE EMC requirements does not guarantee
an entire machine or installation complies with CE EMC requirements.
Many factors can influence total machine/installation compliance.

PowerFlex drives can generate conducted low frequency disturbances
(harmonic emissions) on the AC supply system.

Essential Requirements for CE Compliance

Conditions 1-6 listed below must be satisfied for PowerFlex drives to meet the
requirements of EN61800-3.

1.

Standard PowerFlex 700H or 700S CE compatible Drive. For Frames 10
and up, the drive must also be installed in a suitable Rittal TS 8 (or
equivalent) enclosure.

2.

Review important precautions/attention statements throughout this
manual before installing the drive.

3.

Grounding as described on page

21

.

4.

Output power, control (I/O) and signal wiring must be braided, shielded
cable with a coverage of 75% or better, metal conduit or equivalent
attenuation.

5.

All shielded cables should terminate with the proper shielded connector.

6.

Conditions in

Table 2

.

Table 2 - PowerFlex EN61800-3 EMC Compatibility

Fram

e

Second Environment
Restrict Motor Cable to 30 m (98 ft.)

Any Drive and Option

9

10

11

12

13

14

Advertising
This manual is related to the following products: