Instructions for ATEX Approved PowerFlex 700H Drives in Group II Category (2) Applications with ATEX Approved Motors

Figure 25 - Wiring Example - Internal 24V Power Supply

Configuration

The PowerFlex 700H drive can be configure in one of five ways when using the
20C-DG1 option board, each resulting in the drive being put into a Gate
Disabled state when digital inputs are removed or the thermistor is out of range.

1.

Gate Disable Fault (59):

Configured by setting bit 10 “Gate Disable” of parameter 238 [Fault
Config1].

If both digital inputs open, the drive output will be disabled and the motor
will coast to a stop. The drive HIM will display fault 59 “Gate Disable”.

When the condition is cleared, the fault can be reset and the drive can be
restarted.

If only one digital input opens, the drive output will be disabled and the
motor will coast to a stop. See

Table 25

on page

208

for a description of

drive conditions and actions.

20 24V DC Common

PowerFlex 700H

Control Unit

19 +24V DC

20C-DG1 Disable Option

M

Micro

Controller

Hardware

Disable 1

Motor

Over Temperature

Sensor(s)

Hardware

Disable 2

Slot A

Slot B

2 SD1-

1 SD1+

4 SD2-

3 SD2+

28 TI1+

29 TI1-

PowerFlex 700H

Power Unit

3

Advertising
This manual is related to the following products: