Table 22 - Power Terminal Specifications

Figure 16 - Terminal Locations and Power Terminal Block

No.

Name

Description

Wire Size Range

(1)

Torque

Maximum

Minimum

Recommended

1

Input Power Terminal Block

(2)

L1, L2, L3

Input power

185.0 mm

2

(350 MCM)

95.0 mm

2

(4/0 AWG)

40 N

m

(354 lb

in)

2

Output Power Terminal Block

(2)

U/T1, V/T2, W/T3

Motor connections

185.0 mm

2

(350 MCM)

95.0 mm

2

(4/0 AWG)

40 N

m

(354 lb

in)

3

SHLD Terminal, PE, Motor Ground

Terminating point for wiring shields

95.0 mm

2

(4/0 AWG)

5.0 mm2
(10 AWG)

22 N

m

(195 lb

in)

4

DC Bus

(3)

(2 Terminals; DC–, DC+)

DC input or external brake resistor
(Internal Brake option not provided - See Frame 9 DC Bus/
Brake Connections on
page

68

.)

185.0 mm

2

(350 MCM)

95.0 mm

2

(4/0 AWG)

40 N

m

(354 lb

in)

DC Bus w/Brake

(3)

(3 Terminals; DC–, DC+/R+, R–)

DC input/internal brake
Internal Brake option not provided - See Frame 9 DC Bus/
Brake Connections on
page

68

.)

185.0 mm

2

(350 MCM)

95.0 mm

2

(4/0 AWG)

40 N

m

(354 lb

in)

5

Cable Clamp for Shield

(1) Maximum/minimum sizes that the terminal block will accept - these are not recommendations.
(2) Do Not exceed maximum wire size. Parallel connections may be required.
(3) DC terminal and brake lugs can be removed.

DC

DC+/R+

R–

DC –

DC+/R+

R–

L1

AC Line Input Power

To Motor Leads

L2

L3

L1

L2

L3

U/T1 V/T2 W/T3 U/T1 V/T2 W/T3

DC-, DC+/R+, R- terminals
shown with protective cover
removed.

1

2

3

4

5