Rockwell Automation 20D PowerFlex 700H and 700S Frame 9...14 Drives User Manual

Page 156

Advertising
background image

156

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Chapter 10

Frame 14 Mechanical Installation

Table 31 - Power Terminal Specifications

Figure 64 - 1500A Drive Power Terminal Locations

No. Name

Description

Wire Size Range

(1)(2)

Torque

Terminal Bolt Size

(3)(4)

Maximum

Minimum

Recommended

1

Input Power Terminal Block

(1)

L1, L2, L3

Input power

300 mm

2

(600 MCM)

2.1 mm

2

(14 AWG)

40 N

m

(354 lb

in)

M12

2

Output Power Terminal Block

(3)

U/T1, V/T2, W/T3

Motor connections

300 mm

2

(600 MCM)

2.1 mm

2

(14 AWG)

40 N

m

(354 lb

in)

M12

3

SHLD Terminal, PE, Motor Ground

(3)

Terminating point for wiring shields

300 mm

2

(600 MCM)

2.1 mm

2

(14 AWG)

40 N

m

(354 lb

in)

M10

4

DC Bus

(3)

(3 Terminals; DC–, DC+)

DC input or external brake

300 mm

2

(600 MCM)

2.1 mm

2

(14 AWG)

40 N

m

(354 lb

in)

M12

(1) Maximum/minimum sizes that the terminal block will accept - these are not recommendations.

(2) Do Not exceed maximum wire size. Parallel connections may be required.
(3) These connections are bus bar type terminations and require the use of lug type connectors.
(4) Apply counter torque to the nut on the other side of terminations when tightening or loosening the terminal bolt in order to avoid damage to the terminal.

U/T1

V/T2

W/T3

Side View

U/T1

V/T2

W/T3

L3

L1

L2

Ground Terminals

DC Bus Terminals

Output Power Terminals
without du/dt Filters

Output Power Terminals
with du/dt Filters

Input Power
Terminals

DC–
(Front Terminals)

DC+
(Back Terminals)

Center Enclosure Shown

4

1

2

3

2

Advertising
This manual is related to the following products: