Extension cord recommendations

Any extension cord must have an appropriate wire size for the cord length and system voltage. Use a cord that meets

national and local codes.

The table on the next page provides the recommended gauge sizes for various lengths and input voltages. The lengths

in the tables are the length of the extension cord only; they do not include the power supply’s power cord.

Extension cord specifications

Extension cord length

< 3 m

(< 10 ft)

3–7.5 m

(10–25 ft)

7.5–15 m

(25–50 ft)

15–30 m

(50–100 ft)

30–45 m

(100–150 ft)

200–600 V CSA

Input voltage (VAC)

Phase mm

2

(AWg) mm

2

(AWg) mm

2

(AWg) mm

2

(AWg) mm

2

(AWg)

200–240

3

16 (6)

16 (6)

16 (6)

25 (4)

35 (2)

480–600

3

6 (10)

6 (10)

6 (10)

6 (10)

6 (10)

230400 V CE

Input voltage (VAC)

Phase

mm

2

mm

2

mm

2

mm

2

mm

2

230

3

16

16

16

25

25

400

3

10

10

10

10

10

380 V CCC/230–400 V CE

Input voltage (VAC)

Phase

mm

2

mm

2

mm

2

mm

2

mm

2

230

3

16

16

16

25

25

400

3

10

10

10

10

10

380

3

10

10

10

10

10

400 V CE

Input voltage (VAC)

Phase

mm

2

mm

2

mm

2

mm

2

mm

2

400

3

10

10

10

10

10

380 V CCC

Input voltage (VAC)

Phase

mm

2

mm

2

mm

2

mm

2

mm

2

380

3

10

10

10

10

10