4 Parameter Settings and Functions

4.5.1 Using Servo Alarm and Alarm Code Outputs

4-70

4.5 Forming a Protective Sequence

This section describes the procedure for using I/O signals from the SERVOPACK to form a pro-
tective safety sequence.

4.5.1 Using Servo Alarm and Alarm Code Outputs

The basic procedure for connecting alarm output signals is described below.

Provide an external input power supply; the SERVOPACK does not have an internal 24-V
power supply.

The use of the photocoupler output signals is described below.

These alarms are output when a SERVOPACK alarm is detected.

Photocoupler output

(per output)

Maximum operating voltage:

30 VDC

Maximum output current:

50 mA DC

Open collector output

(per output)

Maximum operating voltage:

30 VDC

Maximum output current:

20 mA DC

50 mA max.

20 mA max.

SERVOPACK

Photocoupler

I/O power supply

Host controller

CN1-31

CN1-32

ALM+

ALM-

+24 V

0 V

CN1-37

CN1-38

CN1-39

ALO1

ALO2

ALO3

SG

CN1-1

0 V

0 V

Output

→ ALM+ CN1-31

Servo Alarm Output

Speed/Torque
Control,
Position Control

Output

→ ALM- CN1-32

Signal Ground for Servo Alarm
Output

Speed/Torque
Control,
Position Control

Turns power OFF.

Alarm

detection

SERVOPACK

ALM output