Cpf01, Display and outputs – Yaskawa Large Capacity Sigma II Series User Manual

Page 373

Advertising
background image

8 Inspection, Maintenance, and Troubleshooting

8.2.1 Troubleshooting Problems with Alarm Displays

8-34

„

CPF01

CPF01: Digital Operator Transmission Error 2
This alarm is not stored in the alarm trace-back function memory.

Display and Outputs

Status and Remedy for Alarm

„

A.- -

A.- -: Normal Operation

This is not an alarm display.

Display and Outputs

Note: OFF:Output transistor is OFF (alarm state). ON: Output transistor is

ON.

Alarm Outputs

Alarm Code Outputs

ALM Output

ALO1

ALO2

ALO3

Not specified

Cause

Remedy

A

Cable defective or poor contact between
Digital Operator and SERVOPACK.

• Check connector connections.
• Replace cable.

B

Malfunction due to external noise.

Separate Digital Operator and cable from
noise source.

C

Digital Operator defective.

Replace Digital Operator.

D

SERVOPACK defective.

Replace SERVOPACK.

Alarm Outputs

Alarm Code Outputs

ALM Output

ALO1

ALO2

ALO3

OFF

OFF

OFF

ON

During operation

A, B, C, D