8 Inspection, Maintenance, and Troubleshooting
8.2.1 Troubleshooting Problems with Alarm Displays
8-34
CPF01
CPF01: Digital Operator Transmission Error 2
This alarm is not stored in the alarm trace-back function memory.
Display and Outputs
Status and Remedy for Alarm
A.- -
A.- -: Normal Operation
This is not an alarm display.
Display and Outputs
Note: OFF:Output transistor is OFF (alarm state). ON: Output transistor is
ON.
Alarm Outputs
Alarm Code Outputs
ALM Output
ALO1
ALO2
ALO3
Not specified
Cause
Remedy
A
Cable defective or poor contact between
Digital Operator and SERVOPACK.
• Check connector connections.
• Replace cable.
B
Malfunction due to external noise.
Separate Digital Operator and cable from
noise source.
C
Digital Operator defective.
Replace Digital Operator.
D
SERVOPACK defective.
Replace SERVOPACK.
Alarm Outputs
Alarm Code Outputs
ALM Output
ALO1
ALO2
ALO3
OFF
OFF
OFF
ON
During operation
A, B, C, D