4.8 Special Wiring

4-99

4

4.8 Special Wiring

This section describes special wiring methods including the one for noise control. In addition to
4.8.1 Wiring Precautions and 4.8.2 Wiring for Noise Control, refer to other sections as neces-
sary.

4.8.1 Wiring Precautions

To ensure safe and stable operation, always observe the following wiring precautions.

1. Always use the following cables for reference input and encoder wiring.

• Trim off the excess portion of the cable to minimize the cable length.

2. For a ground wire, use as thick a cable as possible (2 mm

2

or thicker).

• Ground resistance of 100

Ω max. is recommended.

• Ground to one point only.
• If the motor is insulated from the machine, ground the motor directly.

3. Do not bend or apply tension to cables.

The conductor of a signal cable is very thin (0.2 to 0.3 mm (0.0079 to 0.012 in)), so handle the
cables with care.

4. Use a noise filter to prevent noise interference. (For details, refer to 4.8.2 Wiring for Noise Con-

trol.)

• If the equipment is to be used near private houses or may receive noise interference, install a

noise filter on the input side of the power supply line.

• Since this SERVOPACK is designed as an industrial device, it provides no mechanism to pre-

vent noise interference.

Cable Type

Yaskawa Drawing

No.

Maximum Allow-

able Length

Reference Input

Twisted-pair wires

JZSP-CKI01

3 m (118 in)

Encoder

Multiconductor
shielded twisted-pair
wire

JZSP-CMP09

20 m (787 in)

JZSP-CMP19

50 m (1969 in)