8 Inspection, Maintenance, and Troubleshooting

8.2.1 Troubleshooting Problems with Alarm Displays

8-16

„

A.74

A.74: Overload of Surge Current Limit Resistor

Display and Outputs

Note: OFF:Output transistor is OFF (alarm state). ON: Output transistor is

ON.

Status and Remedy for Alarm

Alarm Outputs

Alarm Code Outputs

ALM Output

ALO1

ALO2

ALO3

ON

ON

ON

OFF

Cause

Remedy

A

Frequently turning the main circuit power
ON/OFF.

Do not repeatedly turn ON/OFF the main
circuit power.

B

Circuit board (1PWB) defective.

Replace SERVOPACK.

When main circuit power
turned ON or OFF

A

At power ON

B