A.74, Display and outputs, Status and remedy for alarm – Yaskawa Large Capacity Sigma II Series User Manual
Page 355
Advertising
8 Inspection, Maintenance, and Troubleshooting
8.2.1 Troubleshooting Problems with Alarm Displays
8-16
A.74
A.74: Overload of Surge Current Limit Resistor
Display and Outputs
Note: OFF:Output transistor is OFF (alarm state). ON: Output transistor is
ON.
Status and Remedy for Alarm
Alarm Outputs
Alarm Code Outputs
ALM Output
ALO1
ALO2
ALO3
ON
ON
ON
OFF
Cause
Remedy
A
Frequently turning the main circuit power
ON/OFF.
Do not repeatedly turn ON/OFF the main
circuit power.
B
Circuit board (1PWB) defective.
Replace SERVOPACK.
When main circuit power
turned ON or OFF
A
At power ON
B