8 Inspection, Maintenance, and Troubleshooting
8.2.1 Troubleshooting Problems with Alarm Displays
8-30
A.d0
A.d0: Position Error Pulse Overflow
Display and Outputs
Note: OFF:Output transistor is OFF (alarm state). ON: Output transistor is
ON.
Status and Remedy for Alarm
Alarm Outputs
Alarm Code Outputs
ALM Output
ALO1
ALO2
ALO3
ON
ON
OFF
OFF
Cause
Remedy
A
Servomotor wiring incorrect.
Check and correct wiring.
B
SERVOPACK was not correctly adjusted.
Increase speed loop gain (Pn100) and posi-
tion loop gain (Pn102).
C
Motor load was excessive.
Reduce load torque and moment of inertia.
Otherwise, replace with larger capacity ser-
vomotor.
D
Position reference pulse frequency was too
high.
• Increase or decrease reference pulse fre-
quency.
• Add smoothing function.
• Correct electronic gear ratio.
E
Circuit board (1PWB) defective.
Replace SERVOPACK.
At power ON
E
During servomotor
operation
Overflow occurs during
high speed rotation
A
Reference pulse is input
properly, but feedback
pulse is not returned.
E
Operation is normal,but
overflow occurs when
long reference is input.
B, C, D