8.2 Troubleshooting

8-29

8

„

A.CC

A.CC: Multiturn Limit Disagreement Alarm

Display and Outputs

Note: OFF:Output transistor is OFF (alarm state). ON: Output transistor is

ON.

Status and Remedy for Alarm

Alarm Outputs

Alarm Code Outputs

ALM Output

ALO1

ALO2

ALO3

ON

OFF

ON

OFF

Cause

Remedy

A

The setting of the Multiturn Limit Setting
(Pn205) parameter in the SERVOPACK is
incorrect.

Change parameter Pn205.

B

The multiturn limit has not been set in the
encoder.

Check to be sure the Multiturn Limit Set-
ting (Pn205) parameter in the SERVO-
PACK is correct, create a Multiturn Limit
Disagreement Alarm (A.CC), and then
execute the encoder multiturn limit setting
change (Fn013).

At power ON

A, B