8.2 Troubleshooting
8-11
8
A.40
A.40: Main Circuit DC Voltage Error Detected: Overvoltage
Display and Outputs
Note: OFF:Output transistor is OFF (alarm state). ON: Output transistor is
ON.
Status and Remedy for Alarm
Alarm Outputs
Alarm Code Outputs
ALM Output
ALO1
ALO2
ALO3
OFF
OFF
ON
OFF
Cause
Remedy
A
The power supply voltage is not within the
range of specifications.
Check power supply.
B
Load exceeds capacity of the Regenerative
Unit.
Check specifications of load moment of
inertia and overhanging load.
C
Regenerative transistor is abnormal.
Replace SERVOPACK.
D
Rectifying diode defective.
E
SERVOPACK defective.
E
A, B, C, D
A, D
Occurred when the
control power turned ON.
During servomotor
operation
Occurred when main
circuit power turned ON.