8.2 Troubleshooting

8-11

8

„

A.40

A.40: Main Circuit DC Voltage Error Detected: Overvoltage

Display and Outputs

Note: OFF:Output transistor is OFF (alarm state). ON: Output transistor is

ON.

Status and Remedy for Alarm

Alarm Outputs

Alarm Code Outputs

ALM Output

ALO1

ALO2

ALO3

OFF

OFF

ON

OFF

Cause

Remedy

A

The power supply voltage is not within the
range of specifications.

Check power supply.

B

Load exceeds capacity of the Regenerative
Unit.

Check specifications of load moment of
inertia and overhanging load.

C

Regenerative transistor is abnormal.

Replace SERVOPACK.

D

Rectifying diode defective.

E

SERVOPACK defective.

E

A, B, C, D

A, D

Occurred when the
control power turned ON.

During servomotor
operation

Occurred when main
circuit power turned ON.