Assertion Levels

When a fault condition occurs on the fan unit or power supply, a signal is
sent to TAC indicating a fault condition. The signal that the fan unit or
power supply sends may use one of the following assertion levels:

Active-High — Signal indicates the assertion state as a logic ONE state.

Active-Low — Signal indicates the assertion state as a logic ZERO state.

The power supply and fan unit assertion levels are configured for the
following parameters (see Table 8-2). Assertion levels are normally set to
active-low, unless otherwise specified by the auxiliary device vendor. The
default is set to active-low.

Table 8-2 Assertion Level Parameters

Parameter

Description

PS-temp

Set to report the temperature of the power
supply.

DC-monitor

Set to report DC current faults of the power
supply.

AC-monitor

Set to report AC current faults of the power
supply.

Fan-temp

Set to report temperature faults of the fan
unit.

Fan-rotation

Set to report rotation faults of the fan unit.