Remote Operation Programming

Table C-4

Remote Operation Programming

Programming Mode

APG

ISOL

Digital

Voltage and Current Output Voltage Programming

0–100%. Voltage control range is 0.0 to 2.0-10.0V in 0.1V increments.

Votage and Current Output Resistive Programming

0-100%. Resistive control range is 0.0 to 2.0 - 10.0K in 0.1K increments.

Output Voltage and Current Monitor

0-100%. Output voltage monitor range is 0.0 to 2.0 - 10.0V in 0.1V increments.

Voltage Programming Accuracy

1

± 0.5% of rated output voltage, max. (0 to 4.0V / 4K Ohm range) ±
0.5% of rated output voltage, typical in other ranges

±0.1% of rated output voltage

Current Programming Accuracy

1

± 1.0% of rated output current, max. (0 to 4.0V / 4K Ohm range) ±
1.0% of rated output current, typical in other ranges

±0.2% of rated output current

Power Programming Accuracy

1

±0.3% of rated output power

Voltage Readback Accuracy

± 1% of range full scale

±0.1% of rated output voltage

Current Readback Accuracy

± 1% of range full scale

±0.2% of rated output current

Power Readback Accuracy

±0.3% of rated output power

Isolation (Prog and Readback Lines)

With respect to chassis potential:
500 V

With respect to:

chassis potential: 600 V .

negative or positive main output: 1500 V .

Voltage and Current Programming Resolution

0.012% of full scale

Power Programming Resolution

OVP Programming Resolution
Voltage and Current Readback Resolution

Power Readback Resolution

Parallel Operation

Up to 4 units in master/slave mode


Series Operation

Up to 2 units (with external diodes)

Constant Voltage (CV)/Constant Current (CC) Indicator

CV: TTL High (4–5 V)
CC: TTL Low (0–0.6 V)

Shutdown Control

2

Logic low 0.0 - 1.4V
Logic high 2.0 - 15V Dry
contact compatible

OUTPUT ENABLE Auxiliary Control

TTL level or dry contact compatible

Power Supply Status Signal

TTL high: OK (4–5 V)
TTL low: fail (0–0.6 V)

Interlock Enable/Disable

Dry contact. Open/Short: On or Off,
programmable

1. Typical APG or isolated APG accuracy can be improved to max accuracy by user calibration at the specific range selected.
2. The shutdown input has user selectable negative logic operation via front panel or remote digital input/output.