Super Systems SuperDATA User Manual
Page 32
Super Systems Inc
Page 32 of 172
Super Data Operations Manual
MMI CARB-PC Instruments
(Note: This instrument may also be polled as a 10PRO. When polled as a CARB-PC polling is done using block mode
and more data is available from the instrument.)
[C]CH#LLL(PPP ) = "ID,[NOLOG],[ABC] " = "tag "
Example:
CH#3(17) = "CARB-PC" = "CH4-CPC"
Note: Items enclosed in brackets [ ] are optional but may be required for certain instrument types.
Item
Definition
C
Optional. Applies to ALL instruments. Specifies the Connection Identifier
(1-8 for serial connections and 9 for Ethernet). The protocol for the
connection must match the protocol for the instrument. If not included,
defaults to Connection 1.
LLL
Required. Applies to ALL instruments.
The logical channel number assigned
(1-128).
PPP
Required. Applies to ALL instruments.
The physical address of the
instrument. (see MMI Instrument Physical Addresses )
ID
Required. Applies to ALL instruments.
The instrument ID: CARB-PC
NOLOG
Optional. Applies to ALL instruments.
Do not log data from this channel.
Include this when communications are required for real-time data but are
not required for historical data logging. If this is not included, the channel
will be data logged at one minute intervals.
ABC
Optional. Applies to ALL instruments.
Alarm Block Configuration .
Caution: any specified channel can use either ALM or ABC but not both.
Allows a custom Alarm Block Bitmap (one word) to be setup for any
instrument but generally used only for non-programmable instruments that
are not capable of maintaining alarm bitmaps. See the section on Custom
Alarm Block Configuration.
TAG
Required. Applies to ALL instruments.
Instrument name. Limited to 12
Characters with no spaces.
Honeywell CPL Instruments
[C]CH#LLL(PPP ) = "ID,[CB:xxx-yyy],…,[CB:xxx-
yyy],[SMULT:SSxVALUE,…,SSxVALUE],[NOLOG],[ABC] " = "tag "
Example:
3CH#34(102)="CPL_HW,CB:256-6,CB:601-4,SMULT:3x100,4x10)="DCP550"
Note: Items enclosed in brackets [ ] are optional but may be required for certain instrument types.
Item
Definition
C
Optional. Applies to ALL instruments. Specifies the Connection Identifier (1-8
for serial connections and 9 for Ethernet). The protocol for the connection
must match the protocol for the instrument. If not included, defaults to
Connection 1.
LLL
Required. Applies to ALL instruments.
The logical channel number assigned (1-
128).
PPP
Required. Applies to ALL instruments.
The physical address of the instrument.
For Honeywell CPL instruments, the address range is 1-127.
ID
Required. Applies to ALL instruments.
The instrument ID: CPL_HW
CB:
Required. Specifies the CPL Data block(s) to be polled. Up to 20 blocks may
be specified. Blocks are specified as xxx-yyy where xxx=address offset and
yyy=count of words to be read. Total word count may not exceed 78 words.