Super Systems SuperDATA User Manual

Page 32

Advertising
background image

Super Systems Inc

Page 32 of 172

Super Data Operations Manual

MMI CARB-PC Instruments

(Note: This instrument may also be polled as a 10PRO. When polled as a CARB-PC polling is done using block mode
and more data is available from the instrument.)

[C]CH#LLL(PPP ) = "ID,[NOLOG],[ABC] " = "tag "

Example:

CH#3(17) = "CARB-PC" = "CH4-CPC"

Note: Items enclosed in brackets [ ] are optional but may be required for certain instrument types.

Item

Definition

C

Optional. Applies to ALL instruments. Specifies the Connection Identifier
(1-8 for serial connections and 9 for Ethernet). The protocol for the
connection must match the protocol for the instrument. If not included,
defaults to Connection 1.

LLL

Required. Applies to ALL instruments.

The logical channel number assigned

(1-128).

PPP

Required. Applies to ALL instruments.

The physical address of the

instrument. (see MMI Instrument Physical Addresses )

ID

Required. Applies to ALL instruments.

The instrument ID: CARB-PC

NOLOG

Optional. Applies to ALL instruments.

Do not log data from this channel.

Include this when communications are required for real-time data but are
not required for historical data logging. If this is not included, the channel
will be data logged at one minute intervals.

ABC

Optional. Applies to ALL instruments.

Alarm Block Configuration .

Caution: any specified channel can use either ALM or ABC but not both.

Allows a custom Alarm Block Bitmap (one word) to be setup for any
instrument but generally used only for non-programmable instruments that
are not capable of maintaining alarm bitmaps. See the section on Custom
Alarm Block Configuration.

TAG

Required. Applies to ALL instruments.

Instrument name. Limited to 12

Characters with no spaces.



Honeywell CPL Instruments


[C]CH#LLL(PPP ) = "ID,[CB:xxx-yyy],…,[CB:xxx-
yyy],[SMULT:SSxVALUE,…,SSxVALUE],[NOLOG],[ABC] " = "tag "

Example:

3CH#34(102)="CPL_HW,CB:256-6,CB:601-4,SMULT:3x100,4x10)="DCP550"


Note: Items enclosed in brackets [ ] are optional but may be required for certain instrument types.

Item

Definition

C

Optional. Applies to ALL instruments. Specifies the Connection Identifier (1-8
for serial connections and 9 for Ethernet). The protocol for the connection
must match the protocol for the instrument. If not included, defaults to
Connection 1.

LLL

Required. Applies to ALL instruments.

The logical channel number assigned (1-

128).

PPP

Required. Applies to ALL instruments.

The physical address of the instrument.

For Honeywell CPL instruments, the address range is 1-127.

ID

Required. Applies to ALL instruments.

The instrument ID: CPL_HW

CB:

Required. Specifies the CPL Data block(s) to be polled. Up to 20 blocks may
be specified. Blocks are specified as xxx-yyy where xxx=address offset and
yyy=count of words to be read. Total word count may not exceed 78 words.