Super Data Operations Manual
6=NOT EQUAL ALARM
7=BIT ON ALARM,
8=BIT OFF ALARM
SLOT: IS THE SLOT TO TEST
CPVAL: IS THE TEST COMPARE VALUE
USE NUMBER FOR CONSTANT VALUE
USE “&SLOT” FOR A SLOT VALUE
USE BIT NUMBER FOR TYPE 7,8 BIT ALARMS
AUXDATA: FOR DEV BAND ALARMS, SPECIFIES THE BANDWIDTH
USE NUMBER FOR CONSTANT VALUE
USE “&SLOT” FOR A SLOT VALUE
Example: ABC01 IS FOR a 10PROE IN BLOCK MODE
ABC01-SALM = 100 *STARTING ALARM NUMBER
ABC01-B0-ALM = 3,36,0,0 *IS PA>0
ABC01-B1-ALM = 0,4,&2,10 *DEV FROM LOCAL SETPOINT, BAND 10DEG
ABC01-B2-ALM = 5,5,0 *TIMER VALUE IS 0
ABC01-B3-ALM = 5,21,1 *CONTROL IN MANUAL
ABC01-B4-ALM = 8,22,0 *USING LOCAL SETPOINT
ABC01-B5-ALM = 3,19,80 *CONTROL OUT ABOVE 80%
Example: ABC02 IS FOR an AACC 2000 (POLLED AS MMIGEN-V4.0, BLK:012)
ABC02-SALM = 200 *STARTING ALARM NUMBER
ABC02-B0-ALM = 0,1,&2,10 *DEV FROM SETPOINT, BAND 10
ABC02-B1-ALM = 3,14,&30 *PROBE RCVY TIME > MAX RCVY TIME
ABC02-B2-ALM = 3,20,90 *CAB TEMP > 90 DEG
ABC02-B3-ALM = 3,22,&27 *PROBE IMP > MAX IMP
ABC02-B4-ALM = 4,10,1400 *PROBE TEMP < 1400 DEG
ABC02-B5-ALM = 4,11,1100 *PROBE MV < 1100
ABC02-B6-ALM = 5,3,1 *CONTROL IN MANUAL
{EABC}