Guidelines for configuring connections, Example 1: drivelogix controller and remote i/o – Rockwell Automation 5720 DriveLogix System User Manual

Page 139

Advertising
background image

Publication 20D-UM002C-EN-P - November 2003

Communicating with Devices on an EtherNet/IP Link 6-23

Guidelines for Configuring
Connections

Each 1788-ENBT communication daughtercard supports 32 I/O
connections. How you configure these connections determines how many
devices the daughtercard can support.

If you have two communication daughtercards, use one for communication
and the other for remote I/O. While one daughtercard can support both
functions, performance can improve by separating these functions onto
separate daughtercards.

Example 1: DriveLogix
Controller and Remote I/O

In the following example, one DriveLogix controller controls remote I/O
through a 1794-AENT module.

Example 1: Controlling remote devices

This example has DriveLogix1 controlling the I/O connected to the remote
1794-AENT module. The data the DriveLogix controller receives from the
remote I/O modules depends on how you configure the remote I/O modules.
You can configure each module as a direct connection or as rack optimized.

!

EtherNet/IP

DriveLogix controller
(DriveLogix1)

EtherNet/IP

1794-AENT with remote I/O
(Remote1)