6-28 Communicating with Devices on an EtherNet/IP Link

Each produced tags requires one connection for the producing controller and
an additional connection for each consuming controller. Each consumed tag
requires one connection.

Example 2: Total connections required by DriveLogix1

The following table calculates the connections used in this example.

If you configured the local I/O modules as rack-optimized, you would only
need the DIN-rail connection to the I/O modules, reducing the above
example by 3 connections.

Connection:

Amount:

DriveLogix1 controller to 3 local I/O modules

rack-optimized connection for the DIN rail

direct connection for each I/O module

1

3

DriveLogix1 controller to local 1788-ENBT

0

DriveLogix1 controller to remote 1788-ENBT

0

connected, cached MSG from DriveLogix1 to
DriveLogix2

1

produced TagA

produced from DriveLogix1 to DriveLogix2

other consumer (2 are configured)

1

1

consumed TagB

1

total connections used: 8