Publication 20D-UM002C-EN-P - November 2003

2-16 What Is DriveLogix?

Connections to DeviceNet devices

In this example the controller uses two connections (one for status and one for
I/O) to communicate with the DeviceNet devices through the 1788-DNBO
module. The 1788-DNBO module uses a rack-optimized connection to the
DeviceNet devices.

The following table calculates the connections in this example.

The 1788-DNBO card does not establish connections to its devices; and
therefore, the controller does not establish connections with DeviceNet
devices. The 1788-DNBO module acts as a scanner that gathers all the data
from its devices and packs that data together into one image that is passed to

Connection:

Amount:

DriveLogix controller to 3 local I/O modules

rack-optimized connection for the DIN rail

direct connection for one I/O module (slot 2)

1

1

DriveLogix controller to the 1788-DNBO DeviceNet
communication card

(1)

(1)

DriveLogix controller connection to remote DeviceNet devices are accounted for in the 2 connections to the
1788-DNBO card.

2

DriveLogix controller to host PowerFlex 700S drive

1

total connections used: 5

PanelView 300

DeviceNet devices

DeviceNet
network

DriveLogix controller

Advertising