Rockwell Automation 5720 DriveLogix System User Manual

Page 53

Advertising
background image

Publication 20D-UM002C-EN-P - November 2003

What Is DriveLogix? 2-19

This example system has these details:

• I/O modules on the local rail are digital, so configure each module for a

rack-optimized connection

• I/O modules on the extended-local rail are analog, so configure each

module for a direct connection

• I/O modules on the ControlNet network are 4 digital and 4 analog, so

configure each digital module for a rack-optimized connection and each
analog module for a direct connection

• there are no produced or consumed tags
• the controller sends 2 messages to other devices on the ControlNet

network

• the controller uses 2 connections to the 1788-DNBO module to collect

data from the DeviceNet devices

Local connections

Remote connections

controller

local rail

8 I/O modules

extended-local rail

8 I/O modules

ControlNet network

8 I/O modules

DeviceNet network

4 DeviceNet devices

Connection Type:

Device
Quantity:

Connections
per Device:

Total
Connections:

rack-optimized connection to DIN rail

2

1

2

connection to host PowerFlex 700S drive

1

1

1

1788-DNBO communication card (rack-optimized connection)

1

2

2

total

5

Connection Type:

Device
Quantity:

Connections
per Device:

Total
Connections:

remote ControlNet communication device

configured as a rack-optimized connection

1

1

1

I/O module over ControlNet (direct connection)

4

1

4

cached message

2

1

2

total

7