Publication 20D-UM002C-EN-P - November 2003

Placing and Configuring the Drive 3-23

Accessing Drive Data

Drive data is displayed as structures of multiple tags. The names and data
structures are based on the selected communication format. The programming
software automatically creates the necessary structures and tags when you
configure the drive module. Each tag name follows this format:

ModuleName:Type.MemberName.SubMemberName.Bit

where:

Refer to Communication Formats on page 3-6 for sample tag names.

Monitoring Drive Data

The DriveLogix controller offers different levels at which you can monitor the
drive module. You can:

• configure the drive module so that the controller faults if the drive loses

its connection to the controller.

• use the programming software to display fault data
• program logic to monitor fault data so you can take appropriate action

This address
variable:

Is:

ModuleName

Identifies the module name entered during the drive module
configuration

Type

Type of data

I = input

O = output

MemberName

Specific data from the drive; depends on the selected
communication format.

For tags associated with pre-defined data links, this name will
be the same as the corresponding parameter name in the drive.

SubMemberName

Specific data related to a MemberName

Bit (optional)

Specific bit of a DINT data value