Drivelogix controller leds – Rockwell Automation 5720 DriveLogix System User Manual

Page 244

Advertising
background image

Publication 20D-UM002C-EN-P - November 2003

A-6 DriveLogix System Specifications

DriveLogix Controller LEDs

Type

Name

Color

State

Description

Daughtercard
LEDs

PORT

Green

Status of DPI port internal communications (if
present).

MOD

Yellow –

Status of communications module (when installed).

NET A

Red

Status of network (if connected).

NET B

Red

Status of secondary network (if connected).

NET A

OFF

No power,

Host is faulted,

Host is holding daughtercard in reset.

Red

Steady

Major Fault

Red

Flashing

Minor Fault

Green

Flashing

No connections established

Green

Steady

Connections established

NET B

OFF

No power,

Host is faulted,

Host is holding daughtercard in reset.

Red

Steady

Major Fault

Red

Flashing

Minor Fault

Green

Flashing

No connections established

Green

Steady

Connections established

Controller
LEDs

RUN

Green

Off

No task(s) running.

Controller in Program mode.

Green

Steady

One or more tasks are running.

Controller is in Run mode.

FORCE

Amber Off

No forces present.

Amber Steady

Forces present and enabled.

Amber Flashing

Forces present but not enabled.

BATT

Red

Off

Battery will support memory.

Red

Steady

Battery may not support memory - replace battery.

I/O

Green

Off

Controller project not downloaded (the condition
after power up).

No I/O or communications configured.

Green

Steady

Communicating to all devices.

Green

Flashing

One or more devices are not responding.

Red

Flashing

No required I/O connections can be made, controller
is in Run mode.

RS 232

Green

Off

No activity.

Green

Flashing

Data being received or transmitted.

OK

Off

No power applied.

Red

Flashing

Recoverable fault or flash programming.

Red

Steady

Controller faulted.

Clear faults, clear memory, or replace the controller.

Green

Steady

Controller OK.

Advertising
This manual is related to the following products: