When the DriveLogix controller initiates messages to PLC or SLC controllers,
you do not have to map compatibility files. You enter the data table address of
the target device just as you would a tag name.

SLC 5/05 controllers, SLC 5/04 controllers (OS402 and above), and
SLC 5/03 controllers (OS303 and above) support logical ASCII addressing
and support PLC/SLC mapping (see the examples above). For all other SLC
or MicroLogix1000 controllers, you must map a PLC-2 compatibility file (see
the PLC-2 examples above).

Producing and
Consuming Data

The DriveLogix controller supports the ability to produce (broadcast) and
consume (receive) system-shared tags over a ControlNet link. Produced and
consumed data is accessible by multiple controllers over a ControlNet
network. Produced and consumed data are scheduled connections because the
controller sends or receives data at a predetermined RPI rate.

Produced and consumed tags must be controller-scoped tags of DINT or
REAL data type, or in an array or structure.

PLC-2 writes to DriveLogix

source element

010

destination tag

200

The destination tag is the three-digit PLC-2 address you specified for PLC-2 mapping.

PLC-5 reads from DriveLogix

SLC reads from DriveLogix

SLC 5/05
SLC 5/04 OS402 and above

SLC 5/03 OS303 and above

source tag

“array_1”

destination element

N7:10

The PLC-5, PLC-3, and SLC controllers support logical ASCII addressing so you do not
have to map a compatibility file for MSG instructions initiated by a PLC-5, PLC-3, or SLC
controller. Place the DriveLogix tag name in double quotes (“).

You could optionally map a compatibility file. For example, if you enter 10 for the
compatibility file, you enter N10:0 for the source tag.

PLC-2 reads from DriveLogix

source tag

200

destination element

010

The source tag is the three-digit PLC-2 address you specified for PLC-2 mapping.

Type of MSG Instruction:

Example Source and Destination:

Tag type:

Description:

Specify:

produced

These are tags that the controller
produced for other controllers to consume.

• Enabled for producing
• How many consumers allowed

consumed

These are tags whose values are produced
by another controller.

• Controller name that owns the tag that the local controller

wants to consume

• Tag name or instance that the controller wants to consume
• Data type of the tag to consume
• Update interval of how often the local controller consumes

the tag

Advertising
This manual is related to the following products: