Publication 20D-UM002C-EN-P - November 2003

6-24 Communicating with Devices on an EtherNet/IP Link

One chassis can have a combination of some modules configured as a direct
connection and others as rack optimized.

Example 1: Total connections required by DriveLogix1

The following table calculates the connections used in this example.

If you configured the remote I/O modules as rack-optimized, you would only
need a rack-optimized connection to the 1794-AENT, reducing the above
example by 3 connections.

Connection:

Amount:

DriveLogix1 controller to 3 local I/O modules

rack-optimized connection for the DIN rail

direct connection for each I/O module

1

3

DriveLogix1 controller to remote 1794-AENT

1

DriveLogix1 to 4 remote I/O modules (through
1794-AENT)

all I/O modules configured as direct connection

no connection to the 1794-AENT

4

total connections used: 9