Rockwell Automation 5720 DriveLogix System User Manual

Page 149

Advertising
background image

Publication 20D-UM002C-EN-P - November 2003

Communicating with Devices on a ControlNet Link 7-3

Step 2: Configure the communication driver

Use RSLinx software to configure the ControlNet communication driver.
Select the appropriate communication driver for the communication
daughtercard in your workstation.

1. In RSLinx software, select Configure Driver. Select the appropriate driver.

The installation instructions for the communications daughtercard should identify which
communication driver to install.

2. Specify the appropriate settings. For example:

If you are using this device:

Specify this information:

1784-KTCx card

memory address, which must match the switch setting on the card

I/O base address, which must match the switch setting on the card

ControlNet node address

1784-PCC card

ControlNet node address (MAC ID)

1784-PCIC card

ControlNet node address (MAC ID)