Communicating with Devices on a ControlNet Link 7-29

The PLC-5 controller supports logical ASCII addressing so you do not have to
map a compatibility file for MSG instructions initiated by a PLC-5 controller.
Place the DriveLogix tag name in double quotes (“).

Example 3: Producing and consuming tags

You can produce and consume tags with any Logix controller the same as you
do with a DriveLogix controller. All Logix controllers follow the same
requirements for producing and consuming tags. See Example 2 above.

Typed Write

SINT or INT tag

any integer element (such as B3:0,
T4:0.ACC, C5:0.ACC, N7:0, etc.)

REAL tag

any floating point element (such as F8:0,
PD10:0.SP, etc.)

Word Range Read

any data type (such as B3:0, T4:0, C5:0,
R6:0, N7:0, F8:0, etc.)

SINT, INT, DINT, or REAL

Word Range Write

SINT, INT, DINT, or REAL

any data type (such as B3:0, T4:0, C5:0,
R6:0, N7:0, F8:0, etc.)

Type of Logix MSG instruction:

Source:

Destination:

Type of MSG Instruction:

Example Source and Destination:

PLC-5 writes to DriveLogix

source element

N7:10

destination tag

“array_1”

PLC-5 reads from DriveLogix

source tag

“array_1”

destination element

N7:10