Publication 20D-UM002C-EN-P - November 2003

7-22 Communicating with Devices on a ControlNet Link

Determining the API

The API (actual packets per interval) is related to the RPI for the connection
and the NUT of the network. Use this table to select the API to enter in the
above worksheet:

Example 1: DriveLogix
Controller and Remote I/O

In the following example, one DriveLogix controller controls remote I/O
through a 1794-ACN15 module.

If:

Enter this value for the API:

RPI

≥ NUT and RPI < 2∗NUT

NUT

RPI

≥ 2∗NUT and RPI < 4∗NUT

2

∗NUT

RPI

≥ 4∗NUT and RPI < 8∗NUT

4

∗NUT

RPI

≥ 8∗NUT and RPI < 16∗NUT

8

∗NUT

RPI

≥ 16∗NUT and RPI < 32∗NUT

16

∗NUT

RPI

≥ 32∗NUT and RPI < 64∗NUT

32

∗NUT

RPI

≥ 64∗NUT and RPI < 128∗NUT

64

∗NUT

RPI

≥ 128∗NUT

128

∗NUT

DriveLogix controller
(DriveLogix1)

ControlNet

1794-ACN with remote I/O
(Remote1)