2-22 What Is DriveLogix?

Selecting a System
Overhead Percentage

The Controller Properties lets you specify a percentage for system overhead.
This percentage specifies the percentage of controller time (excluding the time
for periodic tasks) that is devoted to communication and background
functions

System overhead functions include

• communicating with programming and HMI devices (such as RSLogix

5000 software)

• responding to messages
• sending messages, including block-transfers
• re-establishing and monitoring I/O connections (such as RIUP

conditions); this does not include normal I/O communications that occur
during program execution

• bridging communications from the serial port of the controller to other

communication devices

The controller performs system overhead functions for up to 1 ms at a time. If
the controller completes the overhead functions in less than 1 ms, it resumes
the continuous task.

If communications are not completing fast enough, increase the system
overhead percentage. As you increase the system overhead percentage, the
overall program scan also increases.