Placing and Configuring Local I/O 4-13

To inhibit a module from logic, you must first read the Mode attribute for the
module using a GSV instruction. Set bit 2 to the inhibit status (1 to inhibit or
0 to uninhibit). Use a SSV instruction to write the Mode attribute back to the
module. For example:

Accessing I/O Data

The programming software displays I/O data as structures of multiple tags
that depend on the specific features of the I/O module. The names of the data
structures are based on the location of the I/O module. The programming
software automatically creates the necessary structures and tags when you
configure the module. Each tag name follows this format:

Location:SlotNumber:Type.MemberName.SubMemberName.Bit