Publication 20D-UM002C-EN-P - November 2003

Communicating with Devices on a ControlNet Link 7-27

Example 2: Total connections required by DriveLogix1

The following table calculates the connections used in this example.

If you configured the local I/O modules as rack-optimized, you would only
need the DIN-rail connection to the I/O modules, reducing the above
example by 3 connections.

Connection:

Amount:

DriveLogix1 controller to 3 local I/O modules

rack-optimized connection for the DIN rail

direct connection for each I/O module

1

3

DriveLogix1 controller to local 1788-CNC

0

DriveLogix1 controller to remote 1788-CNC

0

connected, cached MSG from DriveLogix1 to
DriveLogix2

1

produced TagA

produced from DriveLogix1 to DriveLogix2

other consumer (2 are configured)

1

1

consumed TagB

1

total connections used: 8