Using driveexecutive lite – Rockwell Automation 5720 DriveLogix System User Manual

Page 73

Advertising
background image

Publication 20D-UM002C-EN-P - November 2003

Placing and Configuring the Drive 3-15

Using DriveExecutive Lite

In order to launch DriveExecutive Lite from within RSLogix 5000, the drives
power rating must be selected. The drive firmware revision must be applied
prior to selecting the power rating.

2.

In the Controller Organizer, select the PowerFlex 700S drive. Right-click the drive module and select Properties

3.

Select the Power tab.

4.

Select the correct Drive Rating. This data can be found on the PowerFlex 700S data nameplate.

1.

If not already done, enter the drive firmware revision. Click the Finish button to apply the
revision data