7-30 Communicating with Devices on a ControlNet Link

Producing and consuming tags with a ControlNet PLC-5 controller depends
on the type of data.

Producing a tag to a ControlNet PLC-5 controller

To produce a tag that a ControlNet PLC-5 controller can consume:

1. Determine the type of data to produce?

DriveLogix1

TagA

DINT

DriveLogix controller
(DriveLogix2)

ControlNet

ControlLogix controller
(Control1)

ControlNet PLC-5 controller
(PLC5C1)

If:

And you are producing:

Then:

INT

na

A. Create a user-defined data type that contains an array of INTs with an even

number of elements, such as INT[2]. When you produce INTs, you must
produce two or more.

B. Create a produced tag and select the user-defined data type you created.

DINT or REAL Only one DINT or REAL value

Create a produced tag and select the DINT or REAL data type, as appropriate.

More than one DINT or REAL

A. Create a user-defined data type that contains an array of DINTs or REALs,

as appropriate.

B. Create a produced tag and select the user-defined data type you created.