Publication 20D-UM002C-EN-P - November 2003

Placing and Configuring Local I/O 4-5

Configuring a DIN Rail

When you create a DriveLogix project, the programming software
automatically creates the DIN rail for the project. You must configure the
DIN rail.

You must specify these characteristics:

• On the General tab, specify the size of the chassis. Enter the number of

modules (1-8) that you plan to install on the rail. The controller uses this
chassis size to determine the size of tag for the rail’s rack-optimized
data.

• On the Connection tab, specify the RPI. The RPI of the DIN rail

applies to all the I/O modules you install on that DIN rail.

1. In the Controller Organizer, select the local (Local) rail of the controller.

Right-click and select Properties.

2. Specify the configuration options for the rail.

IMPORTANT

Set the RPI of the DIN rail to a minimum of 30 ms. I/O
function will be intermittent if the value is set lower,

IMPORTANT

If there are no modules installed on a rail, make sure to
inhibit that rail.