Rockwell Automation 5720 DriveLogix System User Manual

Page 172

Advertising
background image

Publication 20D-UM002C-EN-P - November 2003

7-26 Communicating with Devices on a ControlNet Link

The consumed tag must have the same data type as the produced tag in the
originating controller. The controller performs type checking to ensure proper
data is being received.

This example shows Flex1 as producing TagA and consuming TagB:

Each produced tags requires one connection for the producing controller and
an additional connection for each consuming controller. Each consumed tag
requires one connection.

DriveLogix1

TagA

DINT

DriveLogix2 (Controller_B)

TagA

DINT

ControlNet

workstation

TagA

TagB

Advertising
This manual is related to the following products: