DriveLogix Back-Up on DeviceNet 12-3

Requirements of the Back-Up

The DriveLogix Back-Up on DeviceNet solution requires that you use the
following:

• RSLogix 5000, version 10 or higher
• 2 DriveLogix controllers, firmware revision 10.x or higher
• 2 1788-DNBO communication cards, firmware revision 2.x or higher

Additional requirements are as follows:

• When setting up the DeviceNet network, you must set the primary and

secondary 1788-DNBO cards to the same node address and reserve the
next node address.

We recommend you set the primary and secondary 1788-DNBO node
addresses to 0 and reserve node 1. However, you can use any successive
node numbers (e.g. 30 and 31).

• All I/O and operator interfaces that required back-up must be on

DeviceNet.

• The scanlists in the two DeviceNet scanner must be identical.

IMPORTANT

Many applications use multiple communications
cards in a DriveLogix controller to communicate with
several networks. This solution requires the software
and DriveLogix controllers use version 10.x or higher.

However, if you are using the 1788-ENBT card in
your application, remember that you must use
software and DriveLogix controllers of version 11.x
or higher.