Panelview firmware messages – Rockwell Automation 2711E-xxxx PanelView Operator Terminals User Manual User Manual

Page 140

Advertising
background image

8–6

Troubleshooting PanelView Terminals

Publication 2711E-821 – January 1998

Mistake Message

What to do:

Cause

The acknowledge for this alarm is outside the
defined address.

The trigger value for the acknowledged
alarm is not within the valid range for the
configured PLC address.

Check that the alarm’s trigger value and
Acknowledge Alarm to PLC tag address
have been configured correctly.

Unknown memory card type. Please replace.

You are using a memory card type that is
not recognized by the terminal.

Replace with a compatible memory card.
See Appendix A, Specifications, for a list of
compatible memory cards.

Value out of range.

A screen object has attempted to write a
value to the PLC that is not within the valid
range for the configured PLC address.

Check that the object’s state values and
PLC address have been properly
configured.

The following table lists the messages that are displayed when the
firmware is booted into the wrong PanelView terminal.

Mistake Message

Cause

What to do:

This Firmware requires a PV 1000e Terminal.

The firmware is booted into the wrong
PanelView terminal. It should be booted into
a PanelView 1000e terminal.

Check if the firmware is on a PCMCIA card
that has been upgraded for a particular
terminal type and then plugged into a
different terminal type.

This Firmware requires a PV 1200/1400e
Terminal.

The firmware is booted into the wrong
PanelView terminal. It should be booted into
a PanelView 1200/1400e terminal.

Check if the firmware is on a PCMCIA card
that has been upgraded for a particular
terminal type and then plugged into a
different terminal type.

This Firmware requires a touch terminal.

The firmware is booted into the wrong
PanelView terminal. It should be booted into
a PanelView touch screen terminal.

Check if the firmware is on a PCMCIA card
that has been upgraded for a particular
terminal type and then plugged into a
different terminal type.

This Firmware requires a keypanel terminal.

The firmware is booted into the wrong
PanelView terminal. It should be booted into
a PanelView keypad terminal.

Check if the firmware is on a PCMCIA card
that has been upgraded for a particular
terminal type and then plugged into a
different terminal type.

PanelView Firmware
Messages

Advertising