Rockwell Automation 2711E-xxxx PanelView Operator Terminals User Manual User Manual
Page 75

4–13
Installing PanelView 1400e Terminals
Publication 2711E-821 – January 1998
To connect the PanelView 1400e terminal to the DH+
network:
1. Remove the Remote I/O and DH+ connector plug from the rear of
the terminal. Figure 4.1 shows its location.
2. Back out plug terminal screws 2 and 1 on the connector. See
Figure 4.11 for plug connection locations.
3. Connect the blue wire to plug terminal 1 and the clear wire to
plug terminal 2. Connect shield and shield drain wire to middle
plug terminal.
4. Tighten the screws to secure the wires.
5. Re-insert the plug into the terminal connector.
Note: If the terminal is the last device on the link, connect a 1/2–watt
terminating resistor across terminals 1 and 2.
•
for 57.6 kilobaud and 115.2 kilobaud, use a 150-ohm resistor
(A-B Part Number 740018-29)
•
for 230 kilobaud, use an 82-ohm resistor (A-B Part Number
740018-23)
To connect the PanelView 1400e terminal to the ControlNet network:
"
Connect a PanelView Terminal to a ControlNet network via a tap
with a 1-meter (39.4-in.) drop cable. Use any tap with one of the
following catalog numbers: 1786-TPS, 1786-TPYS, 1786-TPR,
or 1786-TPYR. See the ControlNet PLC-5 Programmable
Controllers User Manual (A-B publication 1785-6.5.14) for more
information about ControlNet taps.
Note: ControlNet taps contain passive electronics and must be
purchased from Allen-Bradley for the network to function properly.
Note: If the terminal is the last device on the link, connect a 75-ohm,
1-watt terminating resistor to the unused connector on the tap (A-B
Catalog Number 1786-XT).
See the ControlNet PLC-5 Programmable Controllers User Manual
(A-B publication 1785-6.5.14), the ControlNet Communication
Interface Card (A-B publication 1784-5.20), and the ControlNet
Planning and Installation Manual (A-B publication 1786-6.2.1) for
more information about ControlNet.
"
"
"