Rockwell Automation 2711E-xxxx PanelView Operator Terminals User Manual User Manual

Page 60

Advertising
background image

3–14

Installing PanelView 1200e Terminals

Publication 2711E-821 – January 1998

Connecting an External Alarm Relay

The terminal can be used to trigger a remote alarm or warning light
under specific conditions. See Appendix B, Specifications, for the
voltage range of the alarm relay.

!

ATTENTION: Do not use this relay for control
functions of any kind.

To attach a remote alarm or light to the alarm relay connector:

1. Prepare the wires by stripping them of their insulation to a length

of

½ to ¾ of an inch (1 to 2 cm).

2. Turn the screw on the alarm relay connector counterclockwise to

open the wire slot.

3. Insert the wire fully into its appropriate slot. Figure 3.13 shows

the slots.

4. Turn the screw clockwise until the wire is held firmly in place.

5. Repeat the procedure until all three wires are connected.

Figure 3.13 The Remote Alarm Connector

21162

N/O

COM

N/C