Rockwell Automation 2711E-xxxx PanelView Operator Terminals User Manual User Manual

Page 68

Advertising
background image

4–6

Installing PanelView 1400e Terminals

Publication 2711E-821 – January 1998

Figure 4.5 Stud-Mount Keypad Terminal Panel Cutout

4.350”

(110.5 mm)

12.850”

(326.4 mm)

PANEL CUT–OUT LAYOUT

1.500”

(38.1 mm)

5.500”

(139.7 mm)

5.500”

(139.7 mm)

6.425”

(163.2 mm)

8.450”

(214.6 mm)

8.700”

(221.0 mm)

9.156”

(232.6 mm)

6.985”

(177.4 mm)

13.970”

(354.8 mm)

7/32” 18 Holes Typ.

Bezel Border Line

6.700”

(170.2 mm)

6.700”

(170.2 mm)

4.350”

(110.5 mm)

16.900”

(429.3 mm) 8.700”

(221.0 mm)

19.00”

(482.6 mm)

9.50”

(241.3 mm)

8.700”

(221.0 mm)

17.400”

(442.0 mm)

9.156”

(232.6 mm)

ЙЙЙЙЙЙЙЙЙЙЙЙЙЙ

ЙЙЙЙЙЙЙЙЙЙЙЙЙЙ

ЙЙЙЙЙЙЙЙЙЙЙЙЙЙ

ЙЙЙЙЙЙЙЙЙЙЙЙЙЙ

ЙЙЙЙЙЙЙЙЙЙЙЙЙЙ

ЙЙЙЙЙЙЙЙЙЙЙЙЙЙ

ЙЙЙЙЙЙЙЙЙЙЙЙЙЙ

ЙЙЙЙЙЙЙЙЙЙЙЙЙЙ

ЙЙЙЙЙЙЙЙЙЙЙЙЙЙ

ЙЙЙЙЙЙЙЙЙЙЙЙЙЙ

ЙЙЙЙЙЙЙЙЙЙЙЙЙЙ

PANEL CUT–OUT LAYOUT

CL

CL

1.500”

(38.1 mm)

24721b

Mounting Your PanelView 1400e Terminal in a 19-inch Rack

You can mount a PanelView 1400e Stud-Mount Keypad terminal in a
standard EIA 19-inch rack. No additional hardware is required.

To mount the terminal:

1. Place the terminal in the rack, aligning the studs with the holes in

the rack.

2. Insert the terminal until the gasket material is flush with the wall

cutout or panel.

3. Nuts are provided with the stud-mount terminal models. Tighten

the nuts to compress the gasket on the terminal.

Built-in spacers prevent the gasket from being over-compressed. The
tightening torque increases significantly when you reach the correct
compression. At this point the tightening torque should not exceed
10 inch-pounds.

To mount a PanelView 1400e Stud-Mount Touch Screen terminal in
a standard 19-inch EIA rack, you require a Rack Mount Kit (Catalog
No. 2711-NR4).