Rockwell Automation 2711E-xxxx PanelView Operator Terminals User Manual User Manual

Page 70

Advertising
background image

4–8

Installing PanelView 1400e Terminals

Publication 2711E-821 – January 1998

Switching Modes

The terminal operates in Configure and Run modes. Configure mode
lets you set up the terminal and Run mode executes the application
file. To switch between modes, you can use either of the following
methods:

the hardware Mode Select Keyswitch, located at the back of the
terminal.

the Software Mode Switch (available in PanelView firmware
version 3 and above) that you can set to Enable or Disable from
the Terminal Configuration screen. For details, see Mode Switch
in Chapter 5 of this manual.

Note: The terminal communicates with your PLC only when the
terminal is in Run mode, so set it to this mode to monitor and control
your PLC application.

With the optional Remote Keyswitch Assembly, you can access the
Mode Select Keyswitch and RS-232 port from the front of the rack
where the terminal is mounted. It is available in a separate kit (A-B
Catalog Number 2711-NC2). For complete mounting instructions,
refer to Remote Keyswitch and RS-232 Port Assembly Installation
Data
(A-B publication 2711-5.2).

Connecting Power to the Terminal

Power requirements for the terminal are 115 Vac (60 Hz) or 230 Vac
(50 Hz).

Before connecting the power cable to the power connector at the rear
of the terminal, make sure the cable is not carrying power. Because
the terminal has no power switch, connecting the cable will start the
terminal if the cable is live.

Important:

The keyboard port is not currently supported by the
PanelView firmware. Connecting a keyboard could
produce unpredictable results and could reset the
terminal.

"