Installing PanelView 1000e Terminals

Publication 2711E-821 – January 1998

Connecting an External Alarm Relay

The terminal can be used to trigger a remote alarm or warning light
under specific conditions. See Appendix A, Specifications, in this
manual for the voltage range of the alarm relay.

!

ATTENTION: Do not use this relay for control
functions of any kind.

!

ATTENTION: The 1000e external alarm relay is rated
for 24 V ac or dc, and 1.0A. Do not exceed the rated
values. The external alarm relay is different for the 1200e
and 1400e terminals.

To attach a remote alarm or light to the alarm relay connector:

1. Prepare the wires by stripping them of their insulation to a length

of

½ to ¾ of an inch (1 to 2 cm).

2. Turn the screw on the alarm relay plug counterclockwise to open

the wire slot.

3. Insert the wire fully into its appropriate slot. Figure 2.13 shows the

slots.

4. Turn the screw clockwise until the wire is held firmly in place.

5. Repeat the procedure until all three wires are connected.

Figure 2.13 The Remote Alarm Connector

20388

On bottom of PanelView 1000e
Terminal
(Refer to Figure 2.1)

Alarm Relay Plug

Normally
Closed

Common

Normally
Open

No
Connect