Cutout – Rockwell Automation 2711E-xxxx PanelView Operator Terminals User Manual User Manual
Page 38

2–7
Installing PanelView 1000e Terminals
Publication 2711E-821 – January 1998
5. Remove the protective installation label covering the top vents of
the terminal.
!
ATTENTION: Remove the protective installation
label covering the top vents to prevent overheating and
damage to the terminal.
Mounting a Clip-Mount Keypad Terminal in a Panel or Wall
Cutout
To prepare the location:
1. Make the appropriate cutout in the wall or panel location. Figure 2.7
shows the cutout dimensions for the clip-mount terminal.
2. Insert the terminal into the panel or wall cutout.
Figure 2.7 Clip-Mount Keypad Terminal Panel Cutout
24755
16.64
”
(423 mm)
15.35
”
(390 mm)
11.11
”
(282 mm)
Bezel Border Line
CUTOUT
CL
CL
10.11
”
(257 mm)
Eight assembled mounting clips are provided with the clip-mount
keypad terminals; only six clips are used for the mount.
3. Make sure the gasket is installed. If not, NEMA 4X will not be
met.
To install the clips:
1. Install the six mounting clips (2 on top, 2 on bottom, 1 on each
side). The ends of the clips slide into the slots on the terminal.
2. Tighten the mounting clip screws by hand until the gasket seal
contacts the mounting surface uniformly. See Figures 2.8 and 2.9
for details.