Wiring recommendations, Terminal weights, Front panel design – Rockwell Automation 2711E-xxxx PanelView Operator Terminals User Manual User Manual

Page 164

Advertising
background image

Specifications: 1400e Operator Terminal

C–3

Publication 2711E-821 – January 1998

Careful wire routing helps cut down on electrical noise. To reduce
electrical noise, the PanelView 1400e Operator Terminal should be
connected to its own branch circuit. The input power source should
be protected by a fuse or circuit breaker rated at no more than
15 amps. Route incoming power to the PanelView 1400e terminal by
a separate path from the communication cable.

!

ATTENTION: Do not run signal wiring and power
wiring in the same conduit.

Where power and communication lines must cross, they should do so
at right angles. Communication lines can be installed in the same
conduit as low-level, dc I/O lines (less than 10 volts).

Keypad terminal

40.1 lbs (18.2 kg)

Touch screen terminal

38.7 lbs (17.6 kg)

These weights do not include any shipping materials used to package
the terminal.

This section describes front panel design specifications for the
PanelView 1400e keypad and touch screen terminals.

Keypad Terminals

Key Panel:

black powder-coated, cast aluminum with
hard-coated, scratch-resistant polyester surface

Keys:

sealed, stainless steel dome membrane switches with
tactile feedback and an actuation force of 1 lb.
(0.455 kg), mounted on the key panel’s anodized
aluminum backer plate. Keys are rated for 2,000,000
presses.

Window:

95% gloss, hard-coated, scratch-resistant polyester
over chemically strengthened glass

Custom legends can be inserted in the 21 user-configurable function
keys and the Select, Cancel, Raise and Lower keys.

Wiring Recommendations

Terminal Weights

Front Panel Design