Temperature, humidity, and high altitude, Heat generation, Shock and vibration – Rockwell Automation 2711E-xxxx PanelView Operator Terminals User Manual User Manual
Page 152

Specifications: 1000e Operator Terminal
A–9
Publication 2711E-821 – January 1998
The following are temperature, humidity, and altitude requirements
for the PanelView 1000e terminal.
Ambient Operating Temperature Limits
•
Maximum: +50
°
C (+122
°
F)
•
Minimum: 0
°
C (+32
°
F)
Storage Temperature Limits
•
Minimum: -25
°
C (-13
°
F)
•
Maximum: +60
°
C (+140
°
F)
Humidity
•
+50
°
C at 95% humidity (non-condensing)
Maximum Altitude
•
Non-operating or storage: 40,000 feet
•
Operating: 6500 feet
154 BTU/hour typical
290 BTU/hour maximum
The following are shock and vibration specifications for the
PanelView 1000e terminal.
Shock Amplitudes
•
Operating 15 G (peak acceleration)
•
Non-operating 30 G (peak acceleration)
Vibration Amplitudes for Operating Units
Frequency range: 5 to 150 Hz
•
5 to 57 Hz: 0.012
”
peak-to-peak displacement
•
58 to 150 Hz: 2.0 G peak acceleration
Temperature, Humidity,
and High Altitude
Heat Generation
Shock and Vibration