Following are the ac power specifications for the PanelView 1000e
terminal.

Power Supply Type

Switching

Range

90–132, 180–264 V ac
automatic setting by the PanelView 1000e terminal to
match available power supply

Frequency Range

47–63 Hz

Power Consumption

45 W typical
70 W maximum

Volt Amps

60 VA typical
90 VA maximum

PanelView 1000e terminals:

require one fuse for each ac line

has fuses the user can not access

uses Littelfuse 218001, or equivalent, Type T, 1.0 A, 250 Vac,
5 mm x 20 mm

!

ATTENTION: Fuses must be replaced by authorized
service personnel only. PanelView 1000e terminals
contain neutral fuses. Disconnect power before
servicing the unit.

PanelView 1000e terminals support the IBM character set for alarm,
local, and information messages.

PanelView 1000e terminals support:

2.25 MB of Flash memory for application file

PCMCIA card of variable size (depends on user application file),
256 K to 16 MB

RAM tests and Memory Checksum tests can be initiated in the
Terminal Diagnostics screen in Configuration mode.

Form-C Contact

24 V ac Max, 1 amp continuous Max

24 V dc Max, 1 amp continuous Max

Minimum Voltage: 100 mV dc

Minimum Current: 10 mA dc

AC Power

Fuses

Character Set

User Memory

Alarm Relay