5–22

Configuring PanelView Operator Terminals

Publication 2711E-821 – January 1998

The Pass-Through Control Byte is also displayed, if it is defined in
the current application.

You can view the terminal settings and PLC information of the
current DH+ application file in the Terminal Network Setup screen.

To view the terminal network settings:

"

Press the Terminal Network Setup button on the Terminal
Configuration screen.

Important:

For information to be displayed on the screen, an
application must be made current (selected).

The terminal network address and baud rate at which you are
communicating are displayed at the top of the screen. The terminal
network address can be changed by pressing the Up and Down
arrows. The baud rate can also be changed to 57.6K, 115.2K, or
230.4K by pressing the Baud Rate button. The default baud rate
setting is 57.6K.

All nodes (devices) with which your application will communicate
are listed. The terminal network address, Device Type, and Timeout
are displayed in the window. Use the Prev and Next buttons to scroll
through the entries in this window.

Terminal Network Setup
for DH+ Applications