5–17
Configuring PanelView Operator Terminals
Publication 2711E-821 – January 1998
To select the network type for direct application file transfers:
1. In the PanelView Terminal Configuration screen, select Transfer
Setup.
2. Select the Network tab.
3. Select Network Direct as the Address Source.
In the examples below, the first screen displays a ControlNet
Direct transfer. The second screen displays a DH+ Direct transfer.
The Terminal Network Address for a ControlNet network type is
a value between 1 and 99 (decimal). For some ControlNet
versions, address 1 must be assigned to a PLC.
For a DH+ network type, the Terminal Network Address is a
value between 0 and 77 (octal); the default is a 0 value. The Baud
Rate default is 57.6K.