4–12

Installing PanelView 1400e Terminals

Publication 2711E-821 – January 1998

Connecting a Terminal to Your PLC System

Figure 4.11 shows the Remote I/O and DH+

connector on the back of

the terminal. This connects the terminal to the host PLC over Remote
I/O or DH+.

Figure 4.11 Remote I/O and DH+ Connector

20163

1

On rear of PanelView1400e Terminal
(Refer to Figure 4.1)

Remote I/O and DH

+

Plug

provided with installation kit

2

SHIELD

Remote I/O

PanelView Terminal

PLC

Shield

Shield

Pin1 Blue

Pin 1 Blue

Pin 2 Clear

Pin 2 Clear

DH+

PanelView Terminal

PLC

Shield

Shield

Pin1 Blue

Pin 2 Blue

Pin 2 Clear

Pin 1 Clear

To connect the PanelView 1400e terminal over Remote I/O:

1. Remove the Remote I/O and DH+ connector plug from the rear of

the terminal. Figure 4.1 shows its location.

2. Back out plug terminal screws 2 and 1 on the connector. See

Figure 4.11 for plug connection locations.

3. Connect the clear wire to plug terminal 2 and the blue wire to

plug terminal 1. Connect shield and shield drain wire to middle
plug terminal.

4. Tighten the screws to secure the wires.

5. Re-insert the plug into the terminal connector.

Note: If the terminal is the last device on the link, connect a 1/2 watt
terminating resistor across terminals 1 and 2.

for 57.6 kilobaud and 115.2 kilobaud, use a 150-ohm resistor
(A-B Part Number 740018-29)

for 230 kilobaud, use an 82-ohm resistor (A-B Part Number
740018-23)

"