5–15

Configuring PanelView Operator Terminals

Publication 2711E-821 – January 1998

When you set the Address Source to RIO Pass-Through and choose
OK, the terminal validates the Address Source and saves the
Auto-Restart settings. The terminal also de-selects the current
application file to ensure that the new manual Pass-Through rack
assignment does not conflict with existing application file rack
assignments.

Now when you switch to Run mode, the File Transfer screen is
displayed automatically.

PLC Controllers Required for Pass-Through

Important:

Only specific series and revisions of PLC and SLC can
do Pass-Through downloads and uploads. The
following table lists applicable PLCs and SLCs.

Processor

Series

Revision

Valid PLC Racks

Baud Rates

SLC-5/04 (requires SLC 5/04
with OS 4.01 and the 1747-SN
Series B Scanner)

All

All

3 octal

57.6 kbps
115.2 kbps
230.4 kbps

PLC-5/11

All

All

3 octal

57.6 kbps
115.2 kbps
230.4 kbps

PLC-5/15

B

N or later

1–3 octal

57.6 kbps

PLC-5/20

All

All

1–3 octal

57.6 kbps
115.2 kbps
230.4 kbps

PLC-5/20C
PLC-5/20C 1.5

All

All

1–3 octal

57.6 kbps
115.2 kbps
230.4 kbps

PLC-5/20E

All

All

1–3 octal

57.6 kbps
115.2 kbps
230.4 kbps

PLC-5/25

A

J or later

1–7 octal

57.6 kbps

PLC-5/30

A

B or later

1–7 octal

57.6 kbps
115.2 kbps
230.4 kbps

PLC-5/40

A
B

E or later
B or later

1–17 octal

57.6 kbps
115.2 kbps
230.4 kbps

PLC–5/40C
PLC-5/40C 1.5

All

All

1–17 octal

57.6 kbps
115.2 kbps
230.4 kbps

PLC-5/40E

All

All

1–17 octal

57.6 kbps
115.2 kbps
230.4 kbps

PLC-5/60

A
B

E or later
B or later

1–27 octal

57.6 kbps
115.2 kbps
230.4 kbps