Introducing the PanelView Terminals

Publication 2711E-821 – January 1998

The ControlNet network is scheduled to be upgraded to Version 1.5.
To use Version 1.5 of ControlNet, you will have to upgrade all
ControlNet devices, including the firmware on the KTCX card.
Follow all upgrade procedures included in the ControlNet upgrade.
For Version 1.5 availability, contact your Allen-Bradley Sales
Representative.

For information about installing communication cards in the
PanelView terminal see PanelView ISA Card Adapter Installation
Data Sheet
, A-B publication 2711E-5.6.

Important:

The DIP switch settings on the KTCX card must be
configured to work with PanelView. If the settings have
been changed and you want to use the card in the
PanelView terminal, you must use the DIP switches on
the KTCX card to select the following addresses:

Address

Setting

Base Memory

D400:0000

Base I/O

220

Figure 1.3 KTCX Switch Settings – Base Memory Address

Base Memory Address D400:0000

up (1)

down (0)

1 2

1 2 3 4

Figure 1.4 KTCX Switch Settings – Base I/O Address

Base I/O Address 220

up (1)

down (0)

1 2 3 4

For more information, see the documentation that comes with the
KTCX card.

For more information about communication devices for ControlNet,
see the PanelBuilder 1400e Configuration Software for Windows
User Manual
, A-B publication 2711E-819.